🔧 Features & Benefits
-
Thermal‑magnetic trip unit (TM‑D): Adjustable overload protection (70–100 A) with fixed magnetic short‑circuit protection for dependable safety.
-
Fixed‑style mounting: Compact and rugged installation via sturdy backplate design.
-
Compliance: Fully meets IEC 60947‑2, EN 60947‑2 standards and features Class II insulation suitable for switchboards (IEC 60664‑1).
-
Durability: Designed to withstand 30,000 mechanical and 12,000 electrical cycles for long-term reliability.
-
Protection degree: IP40 rated and pollution degree 3 ensures dependable performance in challenging environments.
📐 Dimensions & Physical
-
Size: 105 × 161 × 86 mm (W × H × D)
-
Weight: Approx. 1.5–1.8 kg
🌡 Operating Conditions
-
Impulse withstand voltage (Uimp): 8 kV for enhanced resilience to transient surges.
-
Operating temperature range: –25 °C to +70 °C (storage –50 °C to +85 °C).
✅ Ideal For
Commercial, industrial, and infrastructure settings—perfectly tailored to small‑ and medium‑sized buildings seeking robust electrical protection. Ideal for Class II insulated switchboards.
🌱 Sustainability & Certifications
-
Green Premium product: RoHS & REACh compliant, mercury‑free, and delivered in recyclable packaging.
-
Environmental commitment: Engineered for recyclability and long service life, supporting Schneider Electric’s Net Zero 2050 initiative.
⚙️ Technical Summary (Quick Specs)
| Specification | Details |
|---|---|
| Poles | 3P / 3D |
| Rated Current | 100 A (at 40 °C) |
| Trip Unit | TM‑D (thermal‑magnetic), adjustable 70–100 A |
| Instantaneous Pick‑up (Ii) | 800 A fixed |
| Breaking Capacity (Icu) | 25 kA @ 380–415 VAC; 40 kA @ 220–240 VAC |
| Service Breaking Capacity (Ics) | Matches Icu at respective voltages |
| Mechanical Durability | 30,000 cycles |
| Electrical Durability | 12,000 cycles |
| Mounting & Connection | Fixed mount, screw terminals (front ingress/egress) |
| Insulation & Protection | Class II, IP40, Pollution Degree 3 |
| Rated Impulse Withstand Voltage | 8 kV |
| Operating Temperature Range | –25 °C to +70 °C |
| Dimensions (W × H × D) | 105 × 161 × 86 mm |
| Weight | ~1.5–1.8 kg |
| Ambient Storage Temperature | –50 °C to +85 °C |
🔩 Installation & Support
Includes a front-access toggle actuator and clear contact position indicator for easy operation and status monitoring. Compatible with a wide range of accessories and ideal for DIN‑rail and switchboard installations.