ABB 1SDA101368R1 – Tmax XT7S M 1250 A 3-Pole Fixed MCCB, EKIP DIP LS/I Electronic Trip, Front-Terminals (3 p F F)
Pickup currently not available
Detailed Description
Product Overview
The ABB 1SDA101368R1 is a high-capacity molded-case circuit breaker (MCCB) from the Tmax XT7S M family. This model is rated for 1250 A, is configured as 3-pole (3p) with fixed mounting and front-terminal connection (designation “F F”), and features the EKIP DIP LS/I solid-state electronic trip unit — offering advanced protection and monitoring in industrial power-distribution applications.
Key Specifications
-
Rated current (Iₙ): 1250 A
-
Poles: 3-pole (3p)
-
Trip unit: EKIP DIP LS/I (electronic solid-state release)
-
Mounting / Connection: Fixed, front-terminal (F F) version
-
Rated insulation voltage (Uᵢ): 1000 V
-
Rated operational voltage (Uₑ): up to 690 V AC
-
Short-circuit breaking capacity (Icu):
-
At 380-415 V: 50 kA
-
At 220-240 V: 85 kA
-
-
Power loss per pole: ~57 W (at rated operating conditions)
-
Dimensions: Width 210 mm × Height 268 mm × Depth 178 mm
-
Weight: ~14.758 kg
-
Standards: Complies with IEC 60947-2 (low-voltage switchgear & circuit-breakers)
Features & Benefits
-
High capacity: With 1250 A rating and robust short-circuit performance (50 kA @ 415 V, 85 kA @ 220-240 V), this breaker supports heavy duty applications.
-
Electronic trip unit (EKIP DIP LS/I): Offers adjustable long-time, short-time, instantaneous protection as well as diagnostic capabilities — which enhances selectivity and protection coverage versus traditional thermal-magnetic breakers.
-
Compact footprint: Despite high ratings, the physical dimensions are moderate, aiding integration into panels and switchgear.
-
Front-terminal fixed mounting: Simplifies installation in switchboards and allows easier access for wiring and maintenance.
-
Sustainable design: As part of ABB’s product line, likely aligns with EcoDesign and recyclability initiatives (though confirm via datasheet).
-
Industrial-grade reliability: Designed for demanding environments — high current, frequent operations, fault interruption — with tested mechanical and electrical endurance.
Applications / Use Cases
-
Protection of main feeders, sub-distribution boards in large industrial plants
-
Generator or transformer secondary protection circuits
-
Distribution in commercial buildings, data centres, hospitals where high current ratings and selectivity are needed
-
Upgrades or replacements in switchgear requiring modern electronic trip units and front-access wiring layout
Package & Ordering Info
-
Part number: 1SDA101368R1
-
EAN: 8056221011860
-
Configuration: 3-pole, fixed mounting, front terminals (F F)
-
Supplied as single unit (MOQ = 1) — check stock & lead times.
-
Country of origin: Italy (typical for ABB SACE products) — verify with supplier.
Compliance & Safety
-
Designed to meet IEC 60947-2 standard for circuit‐breakers.
-
High interrupting capacity and modern trip unit reduce risk of failure in fault conditions, improving system reliability.
-
Front-access terminal design improves safety and ease of maintenance.